Aquaval,
Inc. es una empresa dedicada unicamente a ofrecer soluciones
en el campo de las valvulas y equipo de desinfeccion de
cloro gas y generadores de ozono, tanto residencial como
tambien a nivel industrial.
Las
empresas y productos que representamos exclusivamente para
America Latina, estan practicamente donde existan liquidos
y solidos, incluuyendo el mercado farmaceutico y alimenticio.
Contact
your local Sales Representatives
|
|
Dosificador de Gas - Model 1500
Gas
A - Ammonia
B - Carbon Dioxide
C - Chlorine
S - Sulfur Dioxide
Vacuum
Regulator Mounting
1 – Cylinder or manifold mounted with rate valve
2 – Ton container mounted with rate valve
3 – Cylinder or manifold mounted with remote meter
(s) and rate valve
4 – Ton mounted with remote mer(s) and rate
5 – Cylinder or manifold mounted with automatic switchover
6 – Ton mounted with automatic switchover
Available
Gas Flowmeters
1 – 06 ppd (12 g/h)
2 – 1.5 ppd (28 g/h)
3 – 4 ppd (75 g/h)
4 – 10 ppd (200 g/h)
5 – 25 ppd (0.5 kg/h)
6 – 50 ppd (0.9 kg/h)
7 – 100 ppd (2.0 kg/h)
8 – 200 ppd (4.0 kg/h)
9 – 500 ppd (10 kg/h)
Maximum
Capacity
2 - 100 ppd (2.0 kg/h)
V - 200 ppd/4 kg/h
5 - 500 ppd/10 kg/h
Accuracy
Within 4% of maximum flowmeter capacity
Operating Range
20:1, manual, 10:1, automatic
Operating Temperature
Ejector, 35?F to 120?F. Other components: - 20?F to 120?F.
The system operating temperature is largely dependent on
the with draw rate of gas from the cylinder and is a functions
of the existing ambient temperature.
Vacuum Tubing
Connections
Maximum Feed Rate Vacuum Length of Vacuum Tubing
100 ppd (2 kg/h) 3/8” 3/8”
200 ppd (4 kg/h) ½ “ 3/8”
500 ppd (10 kg/h) 5/8” 3/8”
Size Requirement – Distance
Gas feeder can be a few feet to several hundred feed from
the ejector, depending on maximum feed rate and the diameter
of connecting pipe or tubing.
Maximum Feed Rate Length of Vacuum Tubing
PPD (kg/h) 100’ (31m) 200’(61 m) 500’
(153 m)
50 (1) 3/8” 3/8” ½”
100 (2) 3/8” ½” ½”
200 (4) ½” 5/8” ¾”
500 (10) 5/8” ¾” 1”
Ejector Connections
Standard
Nozzle 1”hose and ¾’ NPT
100 ppd (2.0 kg/h) Diffuser 1”hose and ¾”
NPT
200 ppd (4.0 kg/h) Inlet 1 ¼” NPT Optional
1 ½” hose
500 ppd (10 kg/h) Outlet 1 ½” hose 1 ¼”
NPT
Materials of Constructions
ABS, PVC, Polyethylene, tantalum, silver, silver plated
silicon bronze, monel, viton and teflon.
Maximum back pressure at point of application for a standard
ejector is 140 psig. For pressures greater than 140 psig.
Consult factory.
All feed rate capacities shown in this bulletin are for
chlorine. To determine those for other gases, multiply each
chlorine value by:
0.95 for sulfure dioxide
0.50 for ammonia
0.78 for carbon dioxide
Gas Warning
All unattended gas containers and gas feed equipment should
be monitored for leaks. Gas sensitive detector, which will
respond quickly to gas leaks in the atmosphere, should be
installed at each site.
Options and Accessories
Inlet Water Assembly • Isolating Valves Booster Pumps
• Flexible Connectors • Scales Gas • Basks
• Manifolds • Gas Detectors • Corporation
Stops • Automatic Controls • Residual Analyzers
• Floor & Wall Cabinets
|
|